Summary

*#1001*74*11*111110111111111111110111## is the actuator autodiagnostic frame the oracle gateways push together with *1*19*74## when a status request (*#1*74##) reaches the emulated faulty actuator (and the physical MH200 capture behind that finding); the same dimension is also answered on request (*#1001*WHERE*11##) by the lights read on the live F461 and MyHomeServer1 (see Hardware Verification). OWNd returned a generic OWNEvent with who == 1001, so nothing exposed the mask. The bit meanings are marked Open in the oracle, so this PR exposes the mask as sent and interprets nothing. Split out of #139.

Changes

  • OWNd/message/lighting.py: OWNLightingDiagnosticEvent (an OWNEvent subclass, registered for WHO 1001, exported from OWNd.message) exposes diagnostic_mask as sent and cleared_bits (1-based from the left; (6, 21) for the oracle mask, () when every bit is set). Only the single-value bit-string shape is decoded: *#1001*74*11*101*5## (a trailing value) fails closed with diagnostic_mask is None (the first version of this PR would have reported "101"). Other WHO 1001 shapes (*#1001*74##, dimension 12) have diagnostic_mask is None. MyHOME's device_health.py reads who / dimension / dimension_value on the event and is unaffected.
  • scripts/sync_documentation.py + README.md: the WHO catalog row for Lighting now reads **1** / **1001** with the diagnostic class listed (python scripts/sync_documentation.py --update).
  • CHANGELOG.md: entry under [Unreleased] / Added.

State Diagram

stateDiagram-v2
    direction TB

    state "1. Gateway on *#1*74## to a faulty actuator (oracle what19; physical MH200 capture)" as Bus {
        [*] --> Request
        Request --> Fault : *1*19*74## then *#1001*74*11*<24-bit mask>##\nF453, F453AV, F459, F460, F461, MH200N, MyHomeServer1
        Request --> MaskOnly : *#1001*74*11*<mask>## only , MH202
        Request --> What19Only : *1*19*74## only , F454, H4684, MH200
        Request --> Refused : nack / silent , F450
    }

    state "2. OWNMessage.parse of the WHO 1001 frame" as Parse {
        [*] --> Who1001
        Who1001 --> Diagnostic : *#1001*74*11*<bits>## , one value, all 0/1\nOWNLightingDiagnosticEvent, diagnostic_mask as sent, cleared_bits , 6, 21\n, before - generic OWNEvent, nothing exposed
        Who1001 --> NoMask : *#1001*74*11*101*5##, *#1001*74*12*5##\nOWNLightingDiagnosticEvent, diagnostic_mask None , fail closed
    }
Loading

Where are the traces

Subsystem Capture Plant Frames verified by this PR
WHO 1001 dimension 11 after WHAT 19 own-firmware-oracle findings/MH200N/what19.md, physical capture EVID-MH200-WHAT19-FAULT (agree with the emulated output; bits 6 and 21 left Open) physical MH200 *1*19*WHERE## + *#1001*WHERE*11*<mask>##
WHO 1001 on a plant without a faulty actuator trace PR: OpenWebNet-HA/MyHOME#799 (merged), f461_live_2026-10-23 run 1 BTicino F461 2.0.11 *#1001*74## NACK (no WHO 1001 device on this plant)
WHO 1001 dimension 11 read on request (2026-10-24, plain OWNd master as sender) capture on file, to be ingested with the next trace PR BTicino F461 2.0.11, healthy BT-F411/4 lights 06 / 07 *#1001*06*11## -> *#1001*06*11*111111111111111101101111## (ACK 120 ms), same for 07; group *#1001*0*11## NACK after 3.0 s but *#1001*05*11*…##, 06, 07, 09 and *#1013*257*11*111111111111111111111111## arrive on the event session
same capture on file MyHomeServer1 3.87.13, healthy lights *#1001*0014*11## and *#1001*0010*11## -> same mask 111111111111111101101111 (ACK 139 / 157 ms); group *#1001*0*11## ACK after 3.7 s with *#1001*0*11*111111111111111101101111## on the command session, about 80 per-device masks and *#1013*256*11*…## on the event session

What does the Oracle say

Suite what19, results/<P>/<V>/oracle/full/what19.tsv, input *#1*74##:

Gateway Reply / verdict Output
F453 010100, F453AV 030014, F459 020105, F460 020012, F461 020011, MH200N 010108, MyHomeServer1 028206 ack / out *1*19*74## then *#1001*74*11*111110111111111111110111##
MH202 010024 ack / out *#1001*74*11*111110111111111111110111## only
F454 020051, H4684 020054, MH200 020102 ack / out *1*19*74## only
F450 020010 nack / silent none

findings/MH200N/what19.md states that the gateway "only translates the bitmask verbatim" and leaves the meaning of bits 6 and 21 Open; this PR exposes the mask and interprets nothing. (The findings page's fleet list omits F453 and MH202; the TSV rows above include them.)

Testing

  • tests/test_who1001_diagnostic_event.py (new, 8 cases): the oracle mask parses as OWNLightingDiagnosticEvent / OWNEvent with where == "74", dimension == 11, the mask kept, cleared_bits == (6, 21) and the log line; an all-ones mask gives (); five other shapes (trailing value, # inside, non-bit characters, dimension 12, a bare dimension 11 request) have no mask; *#1001*74## is not a diagnostic event.
  • Fail before / pass after: on master the module fails at collection (OWNLightingDiagnosticEvent does not exist; with that import removed the WHO 1001 frame is a plain OWNEvent); on this branch all 8 pass.
  • Full suite: 1915 passed, 1 skipped (master: 1907 passed, 1 skipped); 100 % statement coverage, mypy clean, ruff clean, scripts/sync_documentation.py --check (README regenerated in this PR) and scripts/verify_library_standards.py pass.

Live retest (2026-10-24)

Exercised live on 2026-10-24 (table above): dimension 11 is also a readable per-device dimension: the two lights read on each plant answered on request, and the group request made every light that answered (05 / 06 / 07 / 09 on the F461, about 80 WHEREs on the MyHomeServer1) report the same mask 111111111111111101101111 (bits 17 and 20 cleared, counted from the left); this head parses every one of those captured frames as OWNLightingDiagnosticEvent with cleared_bits == (17, 20), while *#1013*25x*11*…## stays OWNGatewayDiagnosticEvent. Inference, unverified: that mask is the healthy pattern of these firmware generations and the oracle's 111110111111111111110111 (bits 6 and 21) the fault pattern; the bit meanings stay open and the decoder interprets nothing. No faulty actuator was available, so the push path (*1*19*WHERE## followed by the mask) rests on the oracle rows only. The MyHomeServer1 group reply with where == "0" is worth a test case; I will add it if you want it in this PR.

Companion

None. Split from #139 (WHO 13 dimension 27 model name).

🤖 Generated with Claude Code

`*#1001*WHERE*11*<mask>##` is the actuator autodiagnostic frame a
gateway pushes with `*1*19*WHERE##` when a status request reaches a
faulty actuator: own-firmware-oracle what19 (input `*michnovka#1*74##`) shows it
on F453, F453AV, F459, F460, F461, MH200N, MyHomeServer1 (after
`*1*19*74##`) and MH202 (alone), and a physical MH200 capture agrees
(findings/MH200N/what19.md, EVID-MH200-WHAT19-FAULT). OWNd returned a
generic OWNEvent with who == 1001 and exposed nothing.

OWNLightingDiagnosticEvent (registered for WHO 1001, exported) exposes
diagnostic_mask as sent and cleared_bits (1-based from the left). The
bit meanings are Open in the oracle, so nothing is interpreted. Only the
single-value bit-string shape is decoded; `*#1001*74*11*101*5##` fails
closed. README WHO catalog lists WHO 1001 (sync_documentation --update).

Co-Authored-By: Claude Fable 5.1 <noreply@anthropic.com>
@codecov-commenter

Copy link
Copy Markdown

⚠️ Please install the 'codecov app svg image' to ensure uploads and comments are reliably processed by Codecov.

Codecov Report

✅ All modified and coverable lines are covered by tests.